Two Stage Compressors

Sr. No.

Compressor Model

Capacity kW

Capacity TR

Shaft Power BkW

1

MX-720

141.30

40.17

111.57

 

 

NOTES

  • Permissible speed limit for all compressors is from 550 rpm to 1000 rpm.
  • Technical details given for two stage compressors are at 1000 rpm speed, ( - ) 30 Deg. C. evaporation and 40 Deg. C. condensing temp for MX-210, MX-310 and MX-420 models and 1000 rpm speed, ( - ) 40 Deg. C. evaporation and 40 Deg. C. condensing temp for models MX-510, MX-630, MX-720,MX-930 and MX-1020 models.
  • These compressors are suitable for other refrigerants too. For details please contact us.

SPECIFICATIONS

Features of Metalex Ammonia Refrigeration Compressor

 

  • Steel fabricated welded compressor housing
  • Options of water cooling
  • Extensive range of single & two stage models
  • Capacity control steps per cylinder
  • Suitable for speed control (500 - 1000 min.-1)

 

Customer Benefits

 

  • Superior COP values at full and part load operation
  • High reliability, high quality wear resistant parts
  • Easy to install, easy to package
  • Low vibration, low noise level
  • Safety design & service friendly
  • Wide capacity range
  • Modest investment and low maintenance cost

APPLICATIONS

  • Poultry slaughter house
  • Multipurpose refrigeration storage
  • Beer and drink industry
  • Industrial ice plants
  • Fish processing industry
  • Cold storages
  • Dairy plants
  • Petrochemical industry
  • Food processing plant

 

DISCLAIMER

Actual colors may vary. This is due to the fact that every computer monitor has a different capability to display colors and that everyone
sees these colors differently. We try to edit our photos to show the samples as life-like as possible, but please understand the actual color
may vary slightly from your monitor. We cannot guarantee that the color you see accurately portrays the true color of the product.

CAPACITY CHART

 

Refrigerant

NH3

Evaporating Temp. in °C

CondensingTemperature

35°C

40°C

Capacity of compressor

Power require

Capacity of compressor

Power require

Qo kW

TR

Pe kW

BHP

Qo kW

TR

Pe kW

BHP

-30

238.70

-

101.70

-

236.40

-

108.50

-

-31

228.20

10.59

99.26

24.00

225.96

10.47

105.88

-

-32

217.70

21.17

96.82

48.01

215.52

20.95

103.26

-

-33

207.20

31.76

94.38

72.01

205.08

31.42

100.64

-

-34

196.70

42.35

91.94

96.02

194.64

41.89

98.02

-

-35

186.20

52.94

89.50

120.02

184.20

52.37

95.40

127.93

-36

177.56

50.48

87.26

117.02

175.62

49.93

92.96

124.66

-37

168.92

48.02

85.02

114.01

167.04

47.49

90.52

121.39

-38

160.28

45.57

82.78

111.01

158.46

45.05

88.08

118.12

-39

151.64

43.11

80.54

108.00

149.88

42.61

85.64

114.84

-40

143.00

40.65

78.30

105.00

141.30

40.17

83.20

111.57

-41

136.02

38.67

76.18

102.16

134.34

38.19

80.86

108.43

-42

129.04

36.69

74.06

99.31

127.38

36.21

78.52

105.30

-43

122.06

34.70

71.94

96.47

120.42

34.24

76.18

102.16

-44

115.08

32.72

69.82

93.63

113.46

32.26

73.84

99.02

-45

108.10

30.73

67.70

90.79

106.50

30.28

71.50

95.88

-46

102.50

29.14

65.66

88.05

100.92

28.69

69.18

92.77

-47

96.90

27.55

63.62

85.31

95.34

27.11

66.86

89.66

-48

91.30

25.96

61.58

82.58

89.76

25.52

64.54

86.55

-49

85.70

24.36

59.54

79.84

84.18

23.93

62.22

83.44

-50

80.10

22.77

57.50

77.11

78.60

22.35

59.90

80.33

-51

75.52

21.47

55.54

74.48

-

-

-

-

-52

70.94

20.17

53.58

71.85

-

-

-

-

-53

66.36

18.87

51.62

69.22

-

-

-

-

-54

61.78

17.56

49.66

66.59

-

-

-

-

-55

57.20

16.26

47.70

63.97

-

-

-

-

Visitors Counter : 136399